We're one of the most professional FA One-stop suppliers in China.Our main products including servo motor, planetary gearbox, inverter and PLC, HMI.Brands including Panasonic, Mitsubishi, Yaskawa, Delta, TECO, Sanyo Denki ,Scheider, Siemens , Omron and etc.; Shipping time: Within 3-5 working days after getting the payment. Payment way: T/T, L/C, PayPal, West Union, Alipay, Wechat and so on
SITOP UPS1600 DC UPS Modules
SITOP 24 V power supplies can be expanded with an uninterrupted power supply (DC UPS) with battery modules for bridging power failures in the order of hours. They prevent expensive downtimes and undefined plant states. In addition, the innovative SITOP UPS1600 offer new options for diagnostics and system integration. The SITOP UPS1600 offers comprehensive functions, open communication via USB or Ethernet/Profinet and is fully integrated in Totally Integrated Automation (TIA).
Specification
input | |
supply voltage at DC rated value | 24 V |
input voltage | DC 21 ... 29 V |
adjustable response value voltage for buffer connection preset | 21.5 V |
adjustable response value voltage for buffer | connection 21 ... 25 V; Adjustable: 21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC |
input current at rated input voltage 24 V rated value | 46 A; for max. charging current (5 A) |
memory | |
type of energy storage | with batteries |
design of the mains power cut bridging-connection | Adjustable range using rotary coding switch: 0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min, max. buffering time |
output | |
utput voltage in normal operation at DC rated value in buffering mode at DC rated value |
24 V 24 V |
formula for output voltage | Vin - approx. 0.2 V |
startup delay time typical | 60 ms |
voltage increase time of the output voltage typical | 60 ms |
output voltage in buffering mode at DC | 18.5 ... 27 V |
output current rated value in normal operation in buffering mode |
40 A 0 ... 120 A 0 ... 120 A |
peak current | 120 A |
property of the output short-circuit proof | Yes |
design of short-circuit protection | Limitation to 3 x I rated for 30 ms/min; through-conductivity for 1.5 x I rated for 5 sec/min |
charging current | 0.1 A, 5 A; Automatically depending on battery module |
Product Application Information
The battery modules that can be connected in parallel, bridge power failures for a few hours supporting the continued operation of processes or parts of them. The function ""Starting from the battery"" means that the UPS1600 can also be used in standalone mode without connection to the supply.
Communication requirements between the DC UPS and the automation components to be protected against power failure can differ. The version of UPS1600 required can be selected accordingly.