Schneider XY2CE2A250 Latching emergency stop rope pull switch

Short Description:

Brand: Schneider 

Product name: Latching emergency stop rope pull switch

Model: XY2CE2A250


We're one of the most professional FA One-stop suppliers in China.Our main products including servo motor, planetary gearbox, inverter and PLC, HMI.Brands including Panasonic, Mitsubishi, Yaskawa, Delta, TECO, Sanyo Denki ,Scheider, Siemens , Omron and etc.; Shipping time: Within 3-5 working days after getting the payment. Payment way: T/T, L/C, PayPal, West Union, Alipay, Wechat and so on

Product Detail

Product Tags

Range of product
Telemecanique Emergency stop rope pull switches XY2C
Product or component type
Latching emergency stop rope pull switch
Device short name
XY2CE
Housing colour
Red RAL 3000
Overvoltage category
Class I conforming to EN/IEC 61140
Class I conforming to NF C 20-030

Local signalling
Without pilot light
Number of cables
1
Trigger cable maximum length
70 m
Body material
Zamak
Cover material
Stainless steel
Reset
By booted push-button
Contacts type and composition
1 NC + 1 NO
Contact operation
Slow-break
Trigger cable anchor point
LH side
Connections - terminals
Screw clamp terminal, 1 x 0.5...2 x 1.5 mm²
Tightening torque
0.8…1.2 N.m
Cable entry number
3 plain hole for Pg 13.5 or ISO M20 cable gland
Safety level
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
Safety reliability data
B10d = 300000 conforming to IEC 60947-5-5 value given for a life time of 20 years limited by mechanical or contact wear
Marking
CE
Mechanical durability
60000 cycles
Distance between cable supports
5 m
[Ie] rated operational current
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current
10 A
[Ui] rated insulation voltage
500 V (pollution degree 3) conforming to EN/IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Positive opening
With conforming to EN/IEC 60947-5-1
Maximum resistance across terminals
25 MOhm conforming to EN/IEC 60255-7 category 3
25 MOhm conforming to NF C 93-050 method A
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60269
Terminals description ISO n°1
(21-22)NC
(13-14)NO
Net weight
1.45 kg
Compatibility code
XY2CE

  • Previous: